ISO/IEC 30134-7:2023
This document specifies the cooling efficiency ratio (CER) as a key performance indicator (KPI) for quantifying the efficient use of energy to control the temperature of spaces within a data centre (DC).
This document:
a) defines the CER of a DC;
b) describes the relationship of this KPI to a DC’s infrastructure, information technology equipment and information technology operations;
c) defines the measurement, the calculation and the reporting of the parameter; and
d) provides information on the correct interpretation of the CER.
Annex A describes the correlation of the CER and other KPIs.
Annex B provides examples of the usage of the CER.
Annex C introduces the parameters that affect the CER.
Annex D describes requirements and recommendations for derivatives of KPIs associated with the CER.
This document is not applicable to cooling systems that are not powered by electricity (e.g. heat-driven absorption chillers).
SDO:
ISO
Language:
English
ICS Codes:
35.020;
91.120.10
Status:
Published
Publish date:
2023-03-09
Standard Number:
ISO/IEC 30134-7:2023