ANSI/CAN//UL/ULC 331B:2024
Scope
1.1 These requirements cover complete, self-contained strainer or filter assemblies intended for use with
the fuels designated in 1.3. Although these devices are designated strainers, they may be either strainers
or filters according to the common terminology of the industry.
1.2 Strainers or filter assemblies for diesel fuel, biodiesel fuel, diesel/biodiesel blends with nominal
biodiesel concentrations up to 20 Percent (B20), kerosene, and fuel oil shall be constructed to comply with
the following:
a) The requirements defined in UL/ULC 331, Standard for Strainers for Flammable and
Combustible Liquids, Anhydrous Ammonia and Non-potable Water; and
b) The requirements in this Standard.
1.3 Strainers and filter assemblies covered by these requirements are intended for use with one or more
of the following:
a) Diesel fuel, which includes renewable diesel, and diesel/biodiesel blends with nominal biodiesel
concentrations up to 5 percent (B0 – B5) formulated in accordance with the Standard Specification
for Diesel Fuel Oils, ASTM D975;
b) Diesel/biodiesel blends and renewable diesel/biodiesel blends with nominal biodiesel
concentrations from 5 percent up to 20 percent (B6 – B20) formulated in accordance with the
Standard Specification for Diesel Fuel Oil, Biodiesel Blends (B6 – B20), ASTM D7467;
c) Biodiesel (B99.9/B100) formulated in accordance with the Standard Specification for Biodiesel
Fuel Blend Stock (B100) for Middle Distillate Fuels, ASTM D6751;
d) Kerosene formulated in accordance with the Standard Specification for Kerosine, ASTM D3699;
e) Fuel oil (heating oil) formulated in accordance with the Standard Specification for Fuel Oils,
ASTM D396.
1.4 These requirements do not cover the following:
a) Strainers for handling liquids under cryogenic conditions;
b) Strainers for marine use;
c) Strainers for automotive fuel lines;
d) Strainers for handling refrigerants;
e) Strainers for use in such facilities as chemical, petrochemical, petroleum, and utility power
plants;
f) Strainers for use in fluid-power (hydraulic and pneumatic) applications;
g) Strainers or filter assemblies for use with gasoline or gasoline/ethanol blends, which are covered
under the Standard for Strainers for Gasoline and Gasoline/Ethanol Blends with Nominal Ethanol
Concentrations Up to 85 Percent (E0 – E85), UL/ULC 331A;
h) Strainers or filter assemblies for use with LP-Gas, Natural Gas, Manufactured Gas, and
Anhydrous Ammonia, which are covered under the Standard for Strainers for Flammable and
Combustible Liquids, Anhydrous Ammonia and Non-potable Water, UL/ULC 331.
1.5 Products covered by this Standard are intended to be installed and used in accordance with the
applicable Codes and Regulations as determined by the Authority Having Jurisdiction (AHJ), such as, but
not limited to:
a) In the United States:
1) Flammable and Combustible Liquids Code, NFPA 30;
2) Code for Motor Fuel Dispensing Facilities and Garages, NFPA 30A; or
3) Standard for the Installation of Oil-Burning Equipment, NFPA 31.
b) In Canada:
1) National Fire Code of Canada;
2) Installation Code for Oil-Burning Equipment, CSA B139;
3) Oil-Burning Equipment: General Requirements, CSA B140; or
4) Provincial or other Regulations.
SDO:
ULC
Language:
English
ICS Codes:
23.100.60;
75.160.20;
75.180.01
Status:
Standard
Publish date:
2024-05-30
Standard Number:
ANSI/CAN//UL/ULC 331B:2024