CSA C22.2 No. 60947-4-1:22
1.1 Scope
This part of IEC 60947 applies to the types of equipment listed in 1.1.1 and 1.1.2 whose main contacts are
intended to be connected to circuits the rated voltage of which does not exceed 1 000 V a.c. or 1 500 V
d.c.
Starters and/or contactors dealt with in this standard are not normally designed to interrupt short-circuit
currents. Therefore, suitable short-circuit protection (see 9.3.4) forms part of the installation but not
necessarily of the contactor or the starter.
In this context, this standard gives requirements for:
– contactors associated with overload and/or short-circuit protective devices;
– starters associated with separate short-circuit protective devices and/or with separate short-circuit and
integrated overload protective devices;
– contactors or starters combined, under specified conditions, with their own short-circuit protective
devices. Such combinations, e.g. combination starters or protected starters are rated as units.
For circuit-breakers and fuse-combination units used as short-circuit protective devices in combination
starters and in protected starters, the requirements of IEC 60947-2 and IEC 60947-3 respectively apply.
Equipment covered by this standard is as follows.
1.1DV.1 D2 Modification of 1.1 by adding the following:
This equipment is intended for installation in accordance with CSA C22.1, Canadian
Electrical Code (CE Code, Part I), and the US National Electrical Code (NEC), NFPA 70.
1.1.1 AC and DC contactors
AC and DC contactors intended for closing and opening electric circuits and, if combined with suitable
relays (see 1.1.2), for protecting these circuits against operating overloads which may occur therein.
NOTE For contactors combined with suitable relays and which are intended to provide short-circuit protection, the relevant conditions
specified for circuit-breakers (IEC 60947-2) additionally apply.
This standard applies also to the actuators of contactor relays and to the contacts dedicated exclusively to
the coil circuit of a contactor.
Contactors or starters with an electronically controlled electromagnet are also covered by this standard.
1.1.1DV.1 D2 Modification of 1.1.1 by adding the following:
This standard also applies to manual controllers and combination motor controllers. See
Annex DVC for specific requirements.
1.1.2 AC motor-starters
AC motor-starters (including motor management starter) intended to start and accelerate motors to normal
speed, to ensure continuous operation of motors, to switch off the supply from the motor and to provide
means for the protection of motors and associated circuits against operating overloads.
For overload relays for starters, including those based on electronic technology with or without extended
functions according to Annex H, the requirements of this standard apply.
1.1.2.1 Direct-on-line (full voltage) a.c. starters
Direct-on-line starters intended to start and accelerate a motor to normal speed, to provide means for the
protection of the motor and its associated circuits against operating overloads, and to switch off the supply
from the motor.
This standard applies also to reversing starters.
1.1.2.2 Reduced voltage a.c. starters
Reduced voltage a.c. starters intended to start and accelerate a motor to normal speed by connecting the
line voltage across the motor terminals in more than one step or by gradually increasing the voltage
applied to the terminals, to provide means for the protection of the motor and its associated circuits against
operating overloads, and to switch off the supply from the motor.
Automatic change-over devices may be used to control the successive switching operations from one step
to the others. Such automatic change-over devices are, for example, time-delay contactor relays or
specified time all-or-nothing relays, under-current devices and automatic acceleration control devices (see
5.10).
1.1.2.2.1 Star-delta starters
Star-delta starters intended to start a three-phase motor in the star connection, to ensure continuous
operation in the delta connection, to provide means for the protection of the motor and its associated
circuits against operating overloads, and to switch off the supply from the motor.
The star-delta starters dealt with in this standard are not intended for reversing motors rapidly and,
therefore, utilization category AC-4 does not apply.
NOTE In the star connection, the starting current in the line and the torque of the motor are about one-third of the corresponding
values for delta connection. Therefore, star-delta starters are used when the inrush current due to the starting is to be limited, or
when the driven machine requires a limited torque for starting. Figure 1 indicates typical curves of starting current, of starting torque
of the motor and of torque of the driven machine.
1.1.2.2.2 Two-step auto-transformer starters
Two-step auto-transformer starters, intended to start and accelerate an a.c. induction motor from rest with
reduced torque to normal speed and to provide means for the protection of the motor and
its associated circuits against operating overloads, and to switch off the supply from the motor.
This standard applies to auto-transformers which are part of the starter or which constitute a unit specially
designed to be associated with the starter.
Auto-transformer starters with more than two steps are not covered by this standard.
The auto-transformer starters dealt with in this standard are not intended for inching duty or reversing
motors rapidly and, therefore, utilization category AC-4 does not apply.
NOTE In the starting position, the current in the line and the torque of the motor related to the motor starting with rated voltage are
reduced approximately as the square of the ratio (starting voltage):(rated voltage). Therefore, auto-transformer starters are used
when the inrush current due to the starting is to be limited or when the driven machine requires a limited torque for starting. Figure 2
indicates typical curves of starting current, of starting torque of the motor and of torque of the driven machine.
1.1.2.3 Rheostatic rotor starters
Starters intended to start an a.c. induction motor having a wound rotor by cutting out resistors previously
inserted in the rotor circuit, to provide means for the protection of the motor against operating overloads
and to switch off the supply from the motor.
This standard applies also to starters for two directions of rotation when reversal of connections is made
with the motor stopped (see 5.3.5.5). Operations including inching and plugging necessitate additional
requirements and are subject to agreement between manufacturer and user.
This standard applies to resistors which are part of the starter or constitute a unit specially designed to be
associated with the starter.