CAN/ULC 102.2:18 (R2024)
1 SCOPE
1.1 This Standard is applicable to the finished surface or covering of a floor extending to a maximum
depth of 65 mm. This method is also applicable to the following:
A Materials which cannot be tested as described in Clause 1.1 of CAN/ULC-S102, Standard
Method of Test for Surface Burning Characteristics of Building Materials and Assemblies,
without the use of supporting material that is not representative of the intended installation;
B Materials which, when tested in the manner described in Clause 1.1 of CAN/ULC-S102,
Standard Method of Test for Surface Burning Characteristics of Building Materials and
Assemblies, melts or drips, or otherwise disintegrates and continues to burn on the floor of the
test chamber;
C Materials designed for use in a relatively horizontal position with only its top surface exposed to
air; or
D Thermoplastic materials.
1.2 Where a material cannot be readily determined to be thermoplastic or thermoset, one test is
conducted in accordance with this standard and one additional test in conformance with requirements of
CAN/ULC-S102, Standard Method of Test for Surface Burning Characteristics of Building Materials and
Assemblies. Triplicate testing shall then be conducted and reported using the method that produces the
highest Flame Spread Value (FSV).
1.3 The primary purpose of this Standard is to determine the comparative burning characteristics of the
material or assembly under test by evaluating the flame spread over its surface when exposed to a test
fire and thus establish a basis on which surface burning characteristics of different materials or assemblies
may be compared, without specific considerations of all the end-use parameters that might affect these
characteristics.
1.4 Smoke Developed Value (SDV) and Flame Spread Value (FSV) are recorded in this Standard. There
is not necessarily a relationship between these two measurements.
1.5 It is the intent of this Standard to register performance during the period of exposure, and not to
determine suitability for use after the test exposure.
1.6 This method does not establish standards of performance for specific applications. It is a means of
evaluating the response of materials, products or assemblies to a particular fire exposure under controlled
laboratory conditions.
SDO:
ULC
Language:
English
ICS Codes:
13.220.40;
13.220.50;
19.040;
91.180
Status:
Standard
Publish date:
2018-05-31
Standard Number:
CAN/ULC 102.2:18 (R2024)