CAN/ULC-S143-14-R2019
1 SCOPE
1.1 The requirements in this Standard apply to non-metallic raceway systems used to enclose optical
fibre cables, communication cables and electrical wires and cables with combustible insulation and jackets
that are rated FT4 and higher designed for use in accordance with CSA C22.1, Canadian Electrical Code,
Part 1, Safety Standard for Electrical Installations, and the National Building Code of Canada.
NOTE 1 : Refer to CSA C22.2 No. 0.3, Test Methods for Electrical Wires and Cables, for additional information on
FT6 and FT4 ratings for cables. See Appendix A for information on FT6 classification.
NOTE 2 : Refer to CSA C22.2 No. 211.0, General requirements and Methods of Testing for Nonmetallic Conduit, for
additional requirements on FT4 ratings for non-metallic raceways for use with cables that are not rated FT4 and
higher.
1.2 The requirements in this Standard apply to non-metallic raceway systems for use with single insulated
conductor and multi-conductor cables that are permitted to be installed either horizontally or vertically in
accordance with CSA C22.1, Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations,
and the National Building Code of Canada.
1.3 Provisions are included in this Standard to allow for an optional measurement of light obscuration in
the combustion stream in the exhaust duct.
SDO:
ULC
Language:
English
ICS Codes:
13.220.20;
29.060.20
Status:
Standard
Publish date:
2014-10-31
Standard Number:
CAN/ULC-S143-14-R2019