CAN/ULC-S2577-13
1.1 These requirements cover suspended ceiling grid low voltage systems and equipment intended for
installation and use in accordance with the:
In Canada:
Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, CSA
C22.1,
In the United States:
National Electrical Code (NEC), ANSI/NFPA 70.
1.2 The suspended ceiling grid low voltage systems covered by this standard are intended to be installed
as a suspended ceiling grid that provides mechanical support for the ceiling tiles and provides electrical
connections between the low voltage power supply and the low voltage equipment. The low voltage
system consists of the following components:
a) An isolating type low voltage power supply with output(s) operating at 30 V (42.4 V peak) or
less and not exceeding Class 2 power limits,
b) A grid rail power distribution system to provide power from the Class 2 power supply to one
or more pieces of Class 2 powered equipment, and
c) Class 2 powered equipment that is electrically connected to the suspended ceiling grid low
voltage system.
1.3 The suspended ceiling grid low voltage system is intended to be permanently connected, for indoor
dry locations, and installed in accordance with the following requirements:
In Canada:
Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, CSA
C22.1, and the National Building Code of Canada.
In the United States:
National Electrical Code (NEC), ANSI/NFPA 70, the International Building Code (IBC),
and the International Mechanical Code (IMC).
This standard also covers suspended ceiling grid low voltage systems intended for use in air-handling
spaces.
10 CAN/ULC-S2577 ? ANSI/UL 2577 FEBRUARY 7, 2013
1.4 This standard does not address any supplemental or alternative requirements for suspended ceiling
grid low voltage systems intended for use in:
In Canada:
a) Hazardous locations as specified in the Canadian Electrical Code, Part I, Safety
Standard for Electrical Installations, CSA C22.1;
b) General patient care areas or critical patient care areas as defined by Section 24 of
the Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, CSA
C22.1; or
c) Emergency systems as defined by Section 46 of the Canadian Electrical Code, Part
I, Safety Standard for Electrical Installations, CSA C22.1.
In the United States:
a) Hazardous locations as specified in the National Electrical Code (NEC), ANSI/NFPA
70;
b) General patient care areas or critical patient care areas as defined by Article 517 of
the National Electrical Code (NEC), ANSI/NFPA 70; or
c) Emergency systems as defined by Article 700 of the National Electrical Code (NEC),
ANSI/NFPA 70.
1.5 This standard does not evaluate the suspended ceiling grid low voltage system for seismic
requirements in accordance with the:
In Canada:
National Building Code of Canada.
In the United States:
International Building Code (IBC).
1.6 This standard does not evaluate the suspended ceiling grid low voltage systems for fire resistance.