CAN/CGSB-3.1000-2007
1. SCOPE
1.1 This standard defines equipment requirements, performance criteria, and operating and testing procedures for the implementation of a vapour control system (VCS) in gasoline distribution networks including terminals, bulk plants, service stations and cargo tanks, commonly known as Stage I. (See Figure 1 for a schematic representation.)
1.1.1 This standard does not include vapour control systems for vehicle refuelling commonly known as Stage II, rail car,
marine transfers or aviation gasoline facilities.
1.2 This standard has been developed to provide regulators, users, installers and compliance authorities with a uniform
installation reference for Stage I vapour control systems.
1.3 Extent of Coverage - This standard provides performance criteria for equipment in use and specifies the type of
interconnecting fittings to be used at terminals, bulk plants and service stations, and on cargo tanks. This standard does not provide design specifications for individual components such as mechanical design of a fitting or detailed piping layout.
1.3.1 This standard also includes procedures for operating the Stage I VCS facilities in the various locations.
Simplified schematics have been provided to illustrate possible field installations and checks.
1.3.2 The test procedures included in this standard provide the basis for assessing the compliance of the equipment and
systems with the requirements of the authority having jurisdiction.
1.4 Application of this Standard - The user of this standard shall refer to the authority having jurisdiction in the application of this standard.
1.5 Certain considerations are required in the application of this standard.
1.5.1 The maximum back-pressure at the cargo tank to provide sufficient head to drive the vapour recovery unit (VRU) is specified as a maximum 4.5 kPa (18 in. of water).
1.5.2 There is a concern with the flow characteristics of poppetted vapour connections. Poppetted adaptors with low
restriction to flow may be necessary for some applications and are recommended for vapour connections to cargo
tanks.
1.5.3 For equipment and safety protection, the use of pressure/vacuum (PV) vents on underground tanks is not
recommended as such devices do not improve vapour recovery.
1.5.4 Flame arrestors conforming to U.S. Underwriters Laboratories Inc. (UL) standards and documents are
recommended in vapour recovery lines for the fire protection of VRU systems. Flame arrestors shall be sized so as not to increase system back-pressures beyond the levels specified in par. 1.5.1.
1.5.5 Present test methods, outlined in section 7, are based on U.S. Environmental Protection Agency (EPA) test methods and data gathered from a large-scale pilot program operated in the Greater Vancouver Regional District (GVRD)
in 1989/1990.
The required information may be obtained by contacting the Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096, U.S.A., telephone 847-272-8800, fax 847-272-8129, Web site www.ul.com.
1.6 Gasoline - Alcohol Blends - The owner/operator of distribution networks handling gasoline-alcohol blends shall
ensure that the materials and processes of the vapour recovery facility are compatible with such blends.
1.7 Quantities and dimensions in this standard are given in metric units with yard/pound equivalents, mostly obtained
through soft conversion, given in parentheses. The metric units shall be regarded as official in the event of dispute
or unforeseen difficulty arising from the conversion.
1.8 This standard requires the use of materials and/or equipment in hazardous situations. This document does not
purport to address all the safety aspects associated with its use. Anyone using this standard has the responsibility
to consult the appropriate authorities and to establish appropriate health and safety practices in conjunction with
any applicable regulatory requirements prior to its use.