1 Scope
1.1 This part of IEC 60079 specifies the construction and testing of
intrinsically safe apparatus, intended for use in potentially explosive
atmospheres and for associated apparatus, which is intended for connection to
intrinsically safe circuits which enter such atmospheres. It also contains
details of the test apparatus previously published as IEC 60079-3.
1.2 This standard supplements IEC 60079-0:1998, the requirements of which apply
to intrinsically safe apparatus and to associated apparatus except as indicated
in the following list.
If associated apparatus is protected by a type of protection listed in IEc
60079-0 then the requirements of that method of protection together with the
relevant parts of IEC 60079-0 also apply to the associated apparatus. The list
of exclusions which follows is directly applicable to associated apparatus
intended for use in situations where there is no potentially explosive
atmosphere and in other circumstances should be used in combination with the
requirements of the other methods of protection.
Clause or subclause excluded
Clause of IEC 60079-0:1998 Intrinsically Associated
safe apparatus
apparatus
3.1 Electrical apparatus Yes Yes
4.2.2 Marking of maximum surface temperature No Yes
5.1 Maximum surface temperature No Yes
5.3 Surface temperature and ignition temperature No Yes
6.2 Enclosure opening delay Yes Yes
7.1.1 Definition of plastics material No Yes
7.1.2 Requirement of plastics material Yes Yes
7.1.3 Verification of plastics material compliance No Yes
7.2 Thermal endurance Yes Yes
7.3 Electrostatic charges on plastics enclosures No Yes
7.3.1 Electrical apparatus of Group I Yes Yes
(notes 1 and 2 only)
7.3.2 Electrical apparatus of Group II Yes Yes
(notes 1 and 2 only)
7.4 Threaded holes in plastics Yes Yes
8.1 Light metal enclosure materials No Yes
8.2 Threaded holes in light metals Yes Yes
9 Fasteners Yes Yes
10 Interlocking devices Yes Yes
11 Bushings Yes Yes
12 Materials used for cementing Yes Yes
14 Connection facilities and terminal compartments Yes Yes
15 Connection facilities for earthing or bonding
conductors Yes Yes
16 Cable and conduit entries Yes Yes
17to 22 Supplementary requirements for certain
electrical apparatus Yes Yes
23.4.3.1Test for resistance to impact Yes Yes
23.4.3.2Drop test (no prior impact test necessary) No Yes
23.4.3.3Required results No Yes
23.4.5 Torque test for bushings Yes Yes
23.4.6.1Temperature measurement No Yes
23.4.6.2Thermal shock test Yes Yes
23.4.7.1
to
23.4.7.7Tests on non-metallic enclosures Yes Yes
23.4.7.8Insulation resistance test of parts of
enclosures of plastics materials No Yes
27.7 Examples of marking Yes Yes
Annex B Ex cable entries Yes Yes
1.3 This standard is applicable to electrical apparatus in which the electrical
circuits themselves are incapable of causing an explosion in the surrounding
explosive atmospheres.
1.4 This stan