ULC-S564-98

Standard for Categories 1 and 2 Foam Liquid Concentrates
1. SCOPe 1.1 The Standards for foam liquid concentrates are divided into three categories: Category 1 Category 2 Category 3 Primarily for use Primarily for use Primarily for use on general purpose on polar solvents, on aircraft rescue hydrocarbon fires oxygenated fuels, firefighting + all and water-miscible Category 1 fuels + all Category 1 applications appalications This Standard refers to Categories 1 and 2 foam liquid concentrates. NOTE: The requirements for Category 3 Aqueous Film-Forming Foam (AFFF) Liquid Concentrates are contained in the Standard CAN/ULC-S560 and the requirements for Category 3 Film-Forming Fluoroprotein (FFFP) Foam Liquid Concentrates are contained in the Standard CAN/ULC-S563. 1.2 These requirements cover foam producing equipment and liquid concentrates employed for the production and discharge of foam that has an expansion ratio of 20:1 or less and is used for fire extinguishment. These requirements are based on the premise that foam equipment and specified types of foam liquid concentrates with which they are intended to be used are to be investigated for use with each other. 1.3 If foam equipment covered by these requirements incorporate sprinklers, the sprinklers shall comply with the requirements for Automatic Sprinklers for Fire-Protection Service, ULC/ORD-C199. 1.4 Requirements for the installation and use of foam equipment and liquid concentrates are included in the following Standards of the National Fire Protection Association: A Standard for Low Expansion Foam, NFPA 11; B Standard for the Installation of Deluge Foam-Water Sprinkler and Foam-Water Spray Systems, NFPA 16; and C Standard for the Installation of Closed-Head Foam-Water Sprinkler Systems, NFPA 16A.
SDO:
ULC
Language:
English
ICS Codes:
13.220.10
Status:
Withdrawn
Publish date:
1998-01-30
Standard Number:
ULC-S564-98