ULC-S564-98
1. SCOPe
1.1 The Standards for foam liquid concentrates are divided into three
categories:
Category 1 Category 2 Category 3
Primarily for use Primarily for use Primarily for use
on general purpose on polar solvents, on aircraft rescue
hydrocarbon fires oxygenated fuels, firefighting + all
and water-miscible Category 1
fuels + all Category 1 applications
appalications
This Standard refers to Categories 1 and 2 foam liquid concentrates.
NOTE: The requirements for Category 3 Aqueous Film-Forming Foam (AFFF) Liquid
Concentrates are contained in the Standard CAN/ULC-S560 and the requirements
for Category 3 Film-Forming Fluoroprotein (FFFP) Foam Liquid Concentrates are
contained in the Standard CAN/ULC-S563.
1.2 These requirements cover foam producing equipment and liquid concentrates
employed for the production and discharge of foam that has an expansion ratio
of 20:1 or less and is used for fire extinguishment. These requirements are
based on the premise that foam equipment and specified types of foam liquid
concentrates with which they are intended to be used are to be investigated for
use with each other.
1.3 If foam equipment covered by these requirements incorporate sprinklers,
the sprinklers shall comply with the requirements for Automatic Sprinklers for
Fire-Protection Service, ULC/ORD-C199.
1.4 Requirements for the installation and use of foam equipment and liquid
concentrates are included in the following Standards of the National Fire
Protection Association:
A Standard for Low Expansion Foam, NFPA 11;
B Standard for the Installation of Deluge Foam-Water Sprinkler and
Foam-Water Spray Systems, NFPA 16; and
C Standard for the Installation of Closed-Head Foam-Water Sprinkler
Systems, NFPA 16A.