6.3-M95
1.1 SCOPE
1.1.1 Types of Regulators. This standard applies to individual gas appliance
pressure regulators, which are not a part of a combination control (see
Part V, Definitions), hereinafter referred to as regulators, intended
for application on individual gas appliances.
This standard also applies to negative gas appliance pressure
regulators (see Part V, Definitions). The performance of negative
pressure regulators is covered under Part III of this standard.
Compliance of a device with this standard does not imply that such
device is acceptable for use on gas appliances without supplemental
tests with the device applied to the particular appliance design.
Components performing functions other than those of a gas appliance
pressure regulator shall comply with the applicable American National
Standards.
1.1.2 Types of Gases. This standard applies to regulators for operations
with natural, manufactured and mixed gases, liquefied petroleum gases
and LP gas-air mixtures.
1.1.3 Regulators shall be classified in accordance with their intended
application with reference to inlet pressures as follows:
Rated
Inlet Pressure
½ psi (3.48 kPa)
2 psi (13.8 kPa)
5 psi (34.5 kPa)
1.1.4 Types of Application. This standard applies to regulators for the
following general types of application:
a. Main burner load application;
b. Pilot burner load application;
c. Main burner and pilot burner load application to control a
minimum pilot flow rate of:
1. 0.15 cubic foot per hour (1.18 cm³/s), P, or
2. 0.50 cubic foot per hour (3.93 cm³/s), P; or
d. Domestic range application (see 2.11).
1.1.5 Mounting Positions(s). The manufacturer shall specify one or more of
the following mounting classifications (see 1.12):
Upright - single position on a horizontal axis with respect to
the inlet connection, as specified by the manufacturer.
Horizontal - any position on a horizontal axis with respect to
the inlet connection.
Vertical - any position on a vertical axis with respect to the
inlet connection.
Limited Horizontal - any position from upright to 90 degrees
(1.57 rad) from upright on a horizontal axis with respect to
the inlet connection.
Multipoise - any position on a horizontal, vertical or
intermediate axis with respect to the inlet connection.
The tests specified herein shall be conducted with the regulator
mounted in the manufacturer's specified upright position, unless
otherwise specified herein.
If the manufacturer specifies more than one mounting position, the test
in 2.8 or 3.8, as applicable, shall be conducted in each mounting
position. The data from these tests shall then be analyzed to
determine the mounting position which produces the minimum outlet
pressure and the mounting position which produces the maximum outlet
pressure, based on results observed for the minimum outlet pressure
setting of the regulator.
a. The tests in 2.9 or 3.9 and 2.10 or 3.10 shall be conducted in
the mounting position which produces the minimum outlet
pressure, as determined in 2.8 or 3.8.
b. The tests in 2.9 or 3.9 and 2.10 or 3.10 shall also be
conducted in the mounting position which produces the maximum
outlet pressure, as determined in 2.8 or 3.8.
1.1.6 The tests specified herein shall be conducted at a room temperature of
77 ± 10°F (25 ± 5.5°C). Regulator