CAN/CSA-Z305.6-92 (R2007)
1.1
This Standard specifies the minimum requirements for a medical oxygen
concentrator central supply system for use as a source of supply in a
nonflammable medical gas piping system which complies with CSA Standard Z305.1.
1.2
Small, portable, "domiciliary" units are not included within the scope of this
Standard.
1.3
This Standard also specifies minimum performance and safety requirements for
the primary, secondary, and reserve supplies; control equipment and alarms; and
pressure-regulating apparatus; along with ancillary equipment necessary to
complete a medical gas central supply system.
1.4
In this Standard, "shall" indicates a mandatory requirement, and "should"
indicates a recommendation, or that which is advised but not mandatory. Notes
accompanying clauses do not include mandatory or alternative requirements. The
purpose of a note accompanying a clause is to separate from the text
explanatory or informative material that is not properly a part of the
Standard. Notes to figures and tables are considered to be part of the figure
or table and are written as mandatory requirements.