Standard for Steel Underground Tanks for Flammable and Combustible Liquids

Logo
ULC Standards Logo
Standards Development Organisation:
Contact Information:
Working Program:
Designation Number:
CAN/ULC-S603-14
Status:
Proceeding to development
SDO Comment Period Start Date:
SDO Comment Period End Date:
Posted On:

Scope:

Scope

1 SCOPE

1.1 Except as described in Clause 1.7, these minimum requirements cover single and double wall

cylindrical steel, non-pressure tanks of the horizontal type that are used for the underground storage of

flammable liquids and combustible liquids, that are compatible with the material of construction.

1.2 These minimum requirements cover double wall tanks with provision for leak detection monitoring of

the interstice between the walls.

NOTE: The designs identified in this Standard are satisfactory for vacuum and/or electronic monitoring devices. (Refer

to Figure 1.)

1.3 This Standard also provides design criteria for integral connections (connection rings/collars) for spill

containment sumps or manway risers.

1.4 These minimum requirements cover tanks, which are fabricated, inspected and tested for leakage

before shipment from the factory as completely assembled vessels.

NOTE: For the requirements for tanks provided with corrosion protection systems at the factory, refer to the Standard

CAN/ULC-S603.1, Standard for External Corrosion Protection Systems for Steel Underground Tanks for Flammable

and Combustible Liquids.

1.5 These minimum requirements cover tanks up to a maximum capacity of 250 000 L.

1.6 The requirements in this Standard are for the construction of stationary tanks and do not cover their

installation, maintenance and operation. The installation, maintenance and operation of these tanks may

be covered by any of, but not limited to, the following documents:

A National Fire Code of Canada, Part 4;

B CSA B139, Installation Code for Oil Burning Equipment;

C API RP 1615, Installation of Underground Petroleum Storage Systems;

D CCME PN 1326, Environmental Code of Practice for Aboveground and Underground Storage

Tank Systems Containing Petroleum and Allied Petroleum Products;

E NFPA 30, Flammable and Combustible Liquids Code; and

F Regulations of the appropriate authority having jurisdiction.

1.7 Where described elsewhere in the Standard, an alternative means of demonstrating compliance is

provided in Subsection 8.3, Alternative Compliance Path. Tank designs subjected to the alternative

compliance path need not be cylindrical. It is intended that proponents will use one of the design-based

approaches identified in the rest of the Standard, or that described in Subsection 8.3, Alternative

Compliance Path, as an equivalent means of obtaining certifications for their products.

1.8 The requirements in this Standard cover products that are integral or built-in to the tank.

NOTE: These requirements do not cover products not integral to the tank, such as spill containment sumps.

Project need:

Project Need
This revision proposal will consist of new and/or modified requirements to address Climate Change Adaptation and Resilience in the standard. The revisions proposed are intended to be invoked by corresponding requirements in the National Codes and other regulations.

Note: The information provided above was obtained by the Standards Council of Canada (SCC) and is provided as part of a centralized, transparent notification system for new standards development. The system allows SCC-accredited Standards Development Organizations (SDOs), and members of the public, to be informed of new work in Canadian standards development, and allows SCC-accredited SDOs to identify and resolve potential duplication of standards and effort.

Individual SDOs are responsible for the content and accuracy of the information presented here. The text is presented in the language in which it was provided to SCC.