Standard Method of Test for the Evaluation of Protective Coverings for Foamed Plastic Insulation - Full-Scale Room Test

Designation Number:
CAN/ULC S145
Standard Type:
National Standard of Canada - Domestic
Standard Development Activity:
Reaffirmation
ICS code(s):
13.220.40; 29.080.99
Status:
Proceeding to development
SDO Comment Period Start Date:
SDO Comment Period End Date:
Posted On:

Scope:

Scope

1.1 The purpose of this test method is to determine the contribution to fire growth of protective coverings over foamed plastic insulation when tested in a Full-Scale Room Test in accordance with CAN/ULC-9705, Fire Tests - Full-Scale Room Test for Surface Products, except as specified in this Standard. 1.2 This test method measures the time to flashover under specified test conditions. Provisions are made to measure smoke obscuration, rate of fire growth and rate of heat release of the protective covering and foamed plastic insulation room lining. 1.3 This test method is not intended to determine the fire resistance rating of wall or ceiling assemblies lined with foamed plastic insulation and a protective covering. In addition, this test method does not identify which products of combustion, nor risks associated with products of combustion. 1.4 This test method provides for classifications of 10 min and 20 min, which are not equivalent to classifications prescribed in CAN/ULC-S124, Standard Method of Test for the Evaluation of Thermal Barriers for Foamed Plastic. Note: See Appendix A for information on the differences between this Standard and CAN/ULC-S124, Standard Method of Test for the Evaluation of Thermal Barriers for Foamed Plastic. 1.5 The exposure test, as described herein, is not intended to be representative of all fire conditions. It is likely that conditions will vary with changes in the amount, nature and distribution of fire loading, ventilation, size and configuration of the assembly installed. These requirements provide a relative measure of the fire performance of comparable assemblies under these specified fire exposure conditions. 1.6 This Standard is used to measure and describe the response of materials, products or assemblies to heat and flame under controlled conditions. 1.7 This Standard includes classifications based on the use of a Full-Scale Room test in accordance with CAN/ULC-9705, Fire Tests - Full-Scale Room Test for Surface Products, but as specified in this Standard. 1.8 It is the intent that classifications shall register performance during a period of exposure and shall not be construed as determining suitability for use after fire exposure. 1.9 The intent of this standard is to evaluate specific combinations of protective materials and foamed plastic insulation as individual systems.

Project need:

Project Need
Reaffirmation of ULC S145; Standard Method of Test for the Evaluation of Protective Coverings for Foamed Plastic Insulation - Full-Scale Room Test

Note: The information provided above was obtained by the Standards Council of Canada (SCC) and is provided as part of a centralized, transparent notification system for new standards development. The system allows SCC-accredited Standards Development Organizations (SDOs), and members of the public, to be informed of new work in Canadian standards development, and allows SCC-accredited SDOs to identify and resolve potential duplication of standards and effort.

Individual SDOs are responsible for the content and accuracy of the information presented here. The text is presented in the language in which it was provided to SCC.