Sealed wire connector systems

Logo
CSA Group
Standards Development Organisation:
Working Program:
Designation Number:
CSA C22.2 NO. 198.2
Standard Type:
National Standard of Canada - Domestic
Standard Sub-Type
Standard Development Activity:
New Edition
ICS code(s):
29.060.20
29.120.20
Status:
Proceeding to development
SDO Comment Period Start Date:
SDO Comment Period End Date:
Posted On:

Scope:

Scope

1.1
The requirements in this standard cover sealed wire connector systems, including insulating caps, covers, resins, tubing, and tapes provided with, or for use with, specific wire connectors. These systems are intended for wet or damp locations, and other installations such as direct burial, below grade, or above grade where protected from direct exposure to sunlight. The wire connectors covered by these requirements are intended for use with copper conductor, aluminum conductor, or both in accordance with installations covered by the National Electrical Code, NFPA 70; the Canadian Electrical Code, Part I, C22.1; and NOM 001 SEDE, Standard for Electrical Installations.

Note 1: Unless marked for the purpose, these wire connector systems have not been evaluated for direct exposure to sunlight. Additional performance considerations to show equivalency to the connected conductors should be considered for UV exposure.

Note 2: These wire connector systems have only been evaluated for fresh water unless marked for direct exposure to salt or seawater.

Note 3: These wire connector systems may also be used indoors.

1.2
These requirements also cover sealed wire connector systems intended for use with single or multiple conductor underground feeder cable, golf course sprinkler cable, underground low energy cable, irrigation cable, or other cable with insulation acceptable for direct burial, below grade use, or wet locations.

1.3
These requirements apply to sealed wire connector systems intended for use with 30 AWG (0.05 mm2) through 2,000 kcmil (1,012 mm2) conductors with currents not exceeding the ampacity of insulated conductors rated either 75°C (167°F) or 90°C (194°F) and intended for use at 1500 V or less.

1.4
This standard does not apply to twist-on style splicing sealed wire connectors.600 V or less.

Project need:

Project Need
This is a tri-national standard that CSA, UL & ANCE have agreed on. The intent of this project is to address clarifications in the scope of the standard and also to make revisions to sunlight resistance and saltwater immersion tests depicted in the standard. This will allow further clarity and continued use of this standard, in addition to updating the current edition based on user feedback.

Note: The information provided above was obtained by the Standards Council of Canada (SCC) and is provided as part of a centralized, transparent notification system for new standards development. The system allows SCC-accredited Standards Development Organizations (SDOs), and members of the public, to be informed of new work in Canadian standards development, and allows SCC-accredited SDOs to identify and resolve potential duplication of standards and effort.