Motor Control Centres

Designation Number:
CSA C22.2 No. 254
Standard Type:
National Standard of Canada - Domestic
Standard Development Activity:
Reaffirmation
Status:
Proceeding to development
SDO Comment Period Start Date:
SDO Comment Period End Date:
Posted On:

Scope:

Scope

1.1 Products covered

 

1.1.1

This Standard applies to motor control centres to be used in accordance with the U.S. National Electrical Code, ANSI/NFPA 70, the Canadian Electrical Code, Part I, CSA C22.1, and the Mexican Electrical Installations (Utility), NOM-001-SEDE.

 

1.1.2

These requirements cover motor control centres for use on circuits having available short-circuit currents not more than 200 000 A rms symmetrical or 200 000 A dc.

 

1.1.3

This Standard applies to single- and three-phase 50 and 60 Hz and dc motor control centres rated not more than 600 V ac or 1 000 V dc.

 

1.1.4

Requirements for fire pump controllers are as provided in Annex C, item 11.

 

1.2 Products not covered

 

These requirements do not cover switchboards or panel boards intended for the control of electric light and power circuits, nor do they cover an individual unit for this purpose. Such units, however, that consist of manually or automatically operated switches, branch-circuit or service-circuit circuit-breakers, over current-protective devices, or the like may be used within a motor control centre.

 

1.3 Equipment

 

1.3.1

A motor control centre can contain, but is not limited to, any combination of equipment such as the following:

 

(a) full-voltage reversing or non-reversing combination motor control units

 

(b) full-voltage multispeed combination motor control units

 

(c) reduced-voltage part-winding, wye-delta or auto-transformer combination motor control units

 

(d) solid-state industrial controllers, such as adjustable-speed drives, programmable controllers, protective relays, and the like

 

(e) lighting or distribution panel boards

 

(f) feeder-tap units

 

(g) incoming-line equipment, such as main lugs, fusible switch, isolation switch, or circuit-breaker

 

(h) control or lighting transformers

 

(i) special equipment assemblies

 

(j) combination contactor units.

 

1.3.2

The foregoing equipment can contain, but is not limited to, such items as push buttons, selector switches, indicating lights, control transformers, control circuit fuses, and auxiliary devices incorporated as an integral part of the units.

Project need:

Project Need
To reaffirm the standard for the 5-year review period

Note: The information provided above was obtained by the Standards Council of Canada (SCC) and is provided as part of a centralized, transparent notification system for new standards development. The system allows SCC-accredited Standards Development Organizations (SDOs), and members of the public, to be informed of new work in Canadian standards development, and allows SCC-accredited SDOs to identify and resolve potential duplication of standards and effort.

Individual SDOs are responsible for the content and accuracy of the information presented here. The text is presented in the language in which it was provided to SCC.