Electromagnetic Compatibility (EMC) - Part 2-12: Environment - Compatibility Levels for Low-Frequency Conducted Disturbances and Signalling in Public Medium-Voltage Power Supply Systems

Logo
CSA Group
Standards Development Organisation:
Working Program:
Designation Number:
CAN/CSA-C61000-2-12-04 (R2018)
Standard Type:
National Standard of Canada - Adoption of International Standard
Standard Development Activity:
Reaffirmation
ICS code(s):
33.100.01
Status:
Proceeding to development
SDO Comment Period Start Date:
SDO Comment Period End Date:
Posted On:

Scope:

Scope

This part of IEC 61000 is concerned with conducted disturbances in the frequency range from 0 kHz to 9 kHz, with an extension up to 148,5 kHz specifically for mains signalling systems. It gives compatibility levels for public medium voltage a.c. distribution systems having a nominal voltage between 1 kV and 35 kV and a nominal frequency of 50 Hz or 60 Hz (see IEC 60038). 

Compatibility levels are specified for electromagnetic disturbances of the types which can be expected in public medium voltage power supply systems, for guidance in:

a) the limits to be set for disturbance emission into public power supply systems (including the planning levels defined in 3.1.5) 

b) the immunity limits to be set by product committees and others for the equipment exposed to the conducted disturbances present in public power supply systems. 

The disturbance phenomena considered are: 

  • voltage fluctuations and flicker 
  • harmonics up to and including order 50 
  • inter-harmonics up to the 50th harmonic 
  • voltage distortions at higher frequencies (above 50th harmonic) 
  • voltage dips and short supply interruptions
  • voltage unbalance
  • transient overvoltages
  • power frequency variation
  • d.c. components
  • mains signalling. 

Most of these phenomena are described in IEC 61000-2-1. In cases where it is not yet possible to establish compatibility levels, some information is provided. 

The medium-voltage systems covered by this standard are public distribution systems supplying either: 

a) private installations in which equipment is connected directly or through transformers
b) substations feeding public low-voltage distribution systems

The compatibility levels specified in this standard apply at the point of common coupling in the case of 

(a) and at the medium-voltage terminals of the substation in the case of 
(b). See Clause 4. 

Project need:

Project Need
To review the Standard within the required 5 year period.

Note: The information provided above was obtained by the Standards Council of Canada (SCC) and is provided as part of a centralized, transparent notification system for new standards development. The system allows SCC-accredited Standards Development Organizations (SDOs), and members of the public, to be informed of new work in Canadian standards development, and allows SCC-accredited SDOs to identify and resolve potential duplication of standards and effort.

Individual SDOs are responsible for the content and accuracy of the information presented here. The text is presented in the language in which it was provided to SCC.