Coated Electrical Sleeving

Designation Number:
CAN/CSA-C22.2 NO. 198.3-05 (R2014)
Standard Type:
National Standard of Canada - Domestic
Standard Development Activity:
Amendment Revision
Status:
Proceeding to development
SDO Comment Period Start Date:
SDO Comment Period End Date:
Posted On:

Scope:

Scope

1.1

The requirements of this Standard apply to Grades A and B acrylic-polymer-coated, silicone-polymer-coated, or vinyl-polymer-coated electrical sleeving that consists of closely woven fabric made from glass (see Table 1 for materials and ratings) and intended for use in equipment designed to be installed and used in accordance with the rules of the Canadian Electrical Code, Part I (CEC), or ANSI/NFPA 70, National Electrical Code (NEC).

 

A product for use at temperatures greater than indicated in Clause 1.2 or a different polymer coating or fibre may be acceptable provided that

(a) it meets the performance tests in this Standard; and

(b) long-term heat-aging tests are conducted as covered in UL 746B or CAN/CSA-C22.2 No. 0.17, using dielectric strength as a primary property and flammability as a secondary property.

 

1.2

These requirements apply to coated electrical sleeving having a standard temperature index classification of 105, 130, 155, 180, 200, 220, and 240 °C.

 

1.3

These requirements apply to coated electrical sleeving intended for use in connection with the internal wiring of electrical devices and appliances located in dry or damp locations where it is not feasible to employ a standard insulated conductor, such as appliance-wiring material, specifically intended for the purpose. Coated electrical sleeving is intended for insulating one or more uninsulated or partially insulated conductors, bus bars, component leads, or assemblies of electrical components. Coated electrical sleeving may be employed in equipment where it is not subjected to repeated flexing or severe mechanical stress.

 

1.4

These requirements apply to oil-resistant coated electrical sleeving intended for occasional or intermittent contact with oil.

 

1.5

These requirements do not apply to unimpregnated or uncoated fabric sleeving, which is generally not considered acceptable for sole (functional) insulation because of the openings inherent in the weave construction of the sleeving fabric.

 

1.6

These requirements do not apply to tubing extruded with reinforcement, extruded electrical tubing, or tubing intended only for mechanical protection, since they are covered by other requirements.

 

1.7

These requirements do not apply to coated electrical sleeving when it is employed as splice insulation in an insulation system above 105 °C (Class A) operation

Project need:

Project Need
To update the Standard based on industry/user needs

Note: The information provided above was obtained by the Standards Council of Canada (SCC) and is provided as part of a centralized, transparent notification system for new standards development. The system allows SCC-accredited Standards Development Organizations (SDOs), and members of the public, to be informed of new work in Canadian standards development, and allows SCC-accredited SDOs to identify and resolve potential duplication of standards and effort.

Individual SDOs are responsible for the content and accuracy of the information presented here. The text is presented in the language in which it was provided to SCC.